There are several ways to wire your CTC, some far better than others. We wanted to provide a little insight to most common of those methods that we see, and their pros and cons.
When we design/build an electrical system we use primarily Method 1 for the safety and longevity of the system. If budget is a high priority we may use Method 2, but we also factor in a lower ampacity on each circuit when using Method 2.
We never use Method 3, which is the most common for trailer manufacturers, simply because it is the cheapest method.
Figure 1
Figure 2
Figure 3
There are a couple important reasons why we prefer the use of standard residential subpanels and 12V fuseblocks as opposed to typical all-in-one RV 120/12V panels.
First is space, while the typical RV panel is UL Listed, we do not believe they offer sufficient wire bending space, or room to work in them.
Second is convenience, while having multiple functions in a single package sounds nice, for electrical it can be an expensive issue.
Repairing vs replacing, if one part fails, you typically have to replace the entire unit since finding replacement parts at a reasonable price can be difficult at best.
Third is cost, the typical WFCO unit will run around $150 as a base 30A RV unit with no breakers.
A residential subpanel will run around $30, a 12V fuseblock less than $20, and a small 12V charger (which if you have solar you do not need) less than $60.
Fourth is practicality, if you are going solar you already have a 12V system so adding another 12V system is not needed.
Figure 4
Easiest way is to route your wire horizontal along the top of the wall using wire clamps to secure every couple feet, then vertical to each outlet. Use aluminum cove to cover wires, then you can easily get to them in the future. Drilling each stud is great in a wood stick frame house, not so much in a metal trailer. See Figure 5
Routing vertical inside walls is a little more work unless you use furring strips to add a little depth to your walls. Often especially in smaller CTCs every inch counts, so channelling your wires is necessary. When you use this method it is best to tape wires in the channel to maintain their route while you re-install panels.
When you need an outlet in a certain location and cannot avoid drilling a metal stud, you must protect that wire as it passes through the stud. This can be done with split loom or bushings. See Figure 6
Figure 5
Figure 6
All boxes have a cubic inch rating stamped in them so an electrician will know how many conductors can safely be in the box, this is for heat dissipation, in other words, Fire Safety.
Also note, the shallow boxes only come with a knockout for a single romex top or bottom, they are not made for multiple romex.
NEC 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. Boxes and conduit bodies shall be of an approved size to provide free space for all enclosed conductors. In no case shall the volume of the box, as calculated in 314.16(A), be less than the fill calculation as calculated in 314.16(B).
(B) Box Fill Calculations The volumes in paragraphs 314.16(B)(1) through (B)(5), as applicable, shall be added together. No allowance shall be required for small fittings such as locknuts and bushings. Each space within a box installed with a barrier shall be calculated separately.
(1) Conductor Fill Each conductor that originates outside the box and terminates or is spliced within the box shall be counted once, and each conductor that passes through the box without splice or termination shall be counted once. Each loop or coil of unbroken conductor not less than twice the minimum length required for free conductors in 300.14 shall be counted twice. The conductor fill shall be calculated using Table 314.16(B). A conductor, no part of which leaves the box, shall not be counted.
(4) Device or Equipment Fill For each yoke or strap containing one or more devices or equipment, a double volume allowance in accordance with Table 314.16(B) shall be made for each yoke or strap based on the largest conductor connected to a device(s) or equipment supported by that yoke or strap. A device or utilization equipment wider than a single 50 mm (2 in.) device box as described in Table 314.16(A) shall have double volume allowances provided for each gang required for mounting.
(5) Equipment Grounding Conductor Fill Where one or more equipment grounding conductors or equipment bonding jumpers enter a box, a single volume allowance in accordance with Table 314.16(B) shall be made based on the largest equipment grounding conductor or equipment bonding jumper present in the box. Where an additional set of equipment grounding conductors, as permitted by 250.146(D), is present in the box, an additional volume allowance shall be made based on the largest equipment grounding conductor in the additional set.
Figure 7
The type of conductor, both the conductor and insulation make a difference in your selection as you can see in the chart below.
The table below will help you choose the correct wire type and gauge for your application.
As you saw in the table above, Cu (copper) is the standard for conductor conductivity at 100%, CCA (Copper Clad Aluminum) is rated at roughly 2/3 of copper or 63% only slightly better than AL (Aluminum) at 61%.
CCA is less expensive making it an attractive option budget wise, but not the best solution electrically speaking.
We do not recommend CCA but if you must use CCA then you need to up size your wire gauge and use less of a load on the circuit, just as if you were using AL conductors.
As with any electrical connection, make sure they are tight and secure, loose connections will create heat and lead to early failure and possibly a fire.
When talking about the length of the circuit, we are referring to total conductor length in DC circuits. This means a device that requires 15 feet of a 2 conductor cable to reach the fuse block is actually a 30 foot circuit. You count both Positive and Negative conductor lengths.
Using the trailer steel as the negative conductor does not eliminate the need to count it as part of the circuit length.
Figure 8
Many instant hot water heaters use batteries for the igniter.
Connecting 3V power to water heater.
An easy way to use your 12V system to power the 3V igniter on the tankless water heater.
We use a step down xfmr like in the link below, it fits perfectly in the battery housing on the unit.
12v Step Down to DC 3V
Figure 9
Figure 10